Digital Integrating Flow rate Meter
MODEL:419B
● Compact 48 x 48 DIN Size
● Dual Display of flow rate and totalizer
● Pulse output for total and 2 x preset output
● Pulse input 419B
Model Designation
| 419B | |
|||
1 |
2 |
3 |
4 |
1. Measuring input
| Code | Measuring range | Input specifications |
Blank |
Non-voltage output or open collector | DC12V 10mA |
RE |
Voltage pulse | "H"=4.5~30V "L"=0~2.0V Approx.5kΩ |
MG |
Tachogenerator | AC0.8~80Vp-p |
SN |
Sine wave | AC0.1~20Vp-p |
2. Power supply voltage
| Code | Power source voltage |
A |
AC100V~240V |
8 |
DC12V±10% |
9 |
DC24V±10% |
3. Power source for sensor
|
||||||||||||||||
4. Analog output, RS-485
| Code | Output specifications | Output impedance | Tolerable Load resistive |
Blank |
- |
||
03 |
DC0~1V | Approx. 0.1MΩ |
200Ω or more |
04 |
DC0~5V | 1kΩ or more | |
05 |
DC0~10V | 2kΩ or more | |
09 |
DC1~5V | 1kΩ or more | |
29 |
DC4~20mA | 5MΩ |
0~500Ω |
E1 |
RS-485 | - |
|
Basic Specifications
| Flow rate
measurement Q = fUP where Q is the flow rate, f is a frequency, U is the user-readable unit of flow(x1, x60, x3600), P is the pulse conversion value |
|
| Flow indication | 0~9999: Red LED,
Character 8mm High, with
zero-suppress function. Decimal point: Programmable form the front key Over-range indication:Display blank: Changeover to be put on or off. |
| Display cycle | Selectable from the front key. 100ms, 400ms, 1s, 2s, 5s |
| Moving averaging | Selectable from the front key. 1, 2, 3, 4, 8, 16-time |
| Pulse conversion value | Selectable from the
front key, from 1x10-6 to
9999 |
| Time base | Selectable from the front key. Seconds, minutes, or hours |
| Accuracy | ± (0.05%+1digit) |
| Flow totalize
measurement The meter displays calculation values which is multiplied numbers of input pulse by the K-factor. Any point can be assigned to initial of total value and be programmed anywhere in the range of the meter. |
|
| Flow indication | 0~99999: Green LED,
Character 8mm High, with
zero-suppress function. 5 or 10 significant digit: Programmable form the front key Over-range indication:Display blank: Changeover to be put on or off. |
| Pulse factor | Programmable Pulse
factor from the front panel. From
1x10-6 to 999,999
pulses/unit. P.O output is synchronized to input pulse when exceeding 1. |
| Primary integrated value | from 0 to 99999, programmable from the front key |
| Display cycle | approx. 0.1s |
| SIG display | Light-up when inputting the signal |
| Common
Specifications |
|
| Input Frequency | HF range:
0.01Hz~10kHz LF range: 0.01Hz~100Hz Programmable from the front key. |
| Min. Pulse width | HF range: 0.05ms / LF range: 5ms |
| Latch / Pose input | Latch: hold display
of instantaneous and integrating
flow rate, and data output (except of Simultaneous pulse output). Accumulated integrated count will be operated. Pose: hold display of instantaneous and integrating flow rate, and data output. Accumulated integrated count will be temporarily stopped. Non-voltage contact or open collector (NPN) DC5V 10mA Active"L", "L"=0~1V, "H"=3.5~5V, 10ms min. Pulse width. |
| Reset | reset to 0 or primary setting value |
| Backup | An EEPROM retains the data of accumulated total flow when the power is interrupted. Keep 10 years. |
| Output | relay contact: AC/DC
150V 80mA |
| Noise filter | 1000V against the power line noises |
| Withstanding Voltage | Input terminals -
Case : AC1500V each for 1 min. Power supply terminals - Case : AC1500V each for 1 min. Power supply terminals - Input and Output terminals : AC1500V each for 1min. Input terminals - Output terminals : AC500V each for 1 min. |
| Insulation Resistance | DC500V 100MΩor more. |
| Power Supply | AC 100 to 240V (50/60HZ), DC12V±10%, DC24V±10% |
| Allowable power | AC 90 to 250V (50/60Hz), DC10.8 to 13.2V, DC21.6 to 26.4V |
| Power Consumption | Approx. 7.5VA at AC100V, 10VA at AC200V, 400mA at DC12V, 250mA at DC24V. |
| Operating Temperature | 0 to 50℃ |
| Storage Temperature | -20 to 70℃ |
| Weight | Approx. 160g |